Table 11. W7 ASD Alarms.

EOI

Display

Function

Description

Possible Causes

CM1

Comm1 Error

Internal communications error.

• Improperly programmed ASD.

• Improper communications settings.

• Improperly connected cables.

CM2

Comm2 Error

External communications error.

EMG

Emergency Off

Output signal from the ASD is
terminated and a brake may be
applied if so configured.

• Stop|Reset pressed twice at the EOI.

• EOFF command received remotely.

• ASD reset required.

MOFF

Main
Undervoltage

Undervoltage condition at the

3-phase AC input to the ASD.

• Low 3-phase utility voltage.

OC

Over Current

ASD output current greater than
the parameter

0601

setting.

• Defective IGBT (U, V, or W).

• ASD output to the motor is connected incorrectly.

Disconnect the motor and retry.

• ASD output phase-to-phase short.

• The ASD is starting into a spinning motor.

• Motor/machine jammed.

• Mechanical brake engaged while the ASD is starting or

while running.

• Accel/Decel time is too short.

• Voltage Boost setting is too high.

• Load fluctuations.

• ASD operating at an elevated temperature.

*OH

Overheat

ASD ambient temperature
excessive.

• ASD is operating at an elevated temperature.

• ASD is too close to heat-generating equipment.

• Cooling fan vent is obstructed (see

Mounting the ASD

on pg. 18

).

• Cooling fan is inoperative.

• Internal thermistor is disconnected.

OJ

Timer

Run-time counter exceeded.

Type Reset required; select Clear run timer.

* Reset ignored if active.