Terminal on pg. 128, St signal selection, St terminal – Toshiba W7 User Manual

Page 134

Advertising
background image

128

W7 ASD Installation and Operation Manual

ST Signal Selection

Program

Terminal Settings

Input Terminals

Other

ST Signal

Selection

This parameter is used to set the operation of the Standby (ST) control terminal
or any terminal configured as the ST terminal.

Settings:

ST-to-CC Required
ST-to-CC Not Required
Interlock with F/R Terminal

The setting ST-to-CC Required enables the ASD for operation so long as the
control terminal ST is connected to CC via a jumper, contact, or other means.

The ST-to-CC Not Required setting allows the ASD to operate without the
ST-to-CC connection. The control terminal ST may be configured for other
functions.

The Interlock with F/R Terminal setting configures the F (Forward) and R
(Reverse) control terminals for the secondary function of Standby. Closing a
set of contacts to either F or R will cause the ASD to accelerate the motor to the
programmed setpoint of F or R. Opening the F and R contact will disable the
ASD and the motor will coast to a stop. The control terminal ST may be
configured for other functions.

Parameter Type — Selection List

Factory Default — ST – CC Required

Changeable During Run — No

ST Terminal

Program

Terminal Settings

Input Terminals

ST

This parameter selects the functionality of the ST discrete input terminal.

In addition, the input terminal must be specified as Normally Open or
Normally Closed.

This parameter sets the programmable ST terminal to 1 of the 69 possible
functions that are listed in

Table 6 on page 138

.

Parameter Type — Selection List

Factory Default — Standby

Changeable During Run — No

ST Signal Selection

ST Terminal