Speed reach setting frequency, Speed reach detection band, Stall prevention during regeneration – Toshiba W7 User Manual

Page 132: Speed drop detection frequency range

Advertising
background image

126

W7 ASD Installation and Operation Manual

Speed Drop Detection Frequency Range

Program

Protection Settings

Speed Drop Detection Frequency

Range

While operating using PG feedback, this parameter sets the lower level of the
deviation limit that, once the output frequency falls below this setting, causes a
Speed Drop Detected alert.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 30.00

Units — Hz

Speed Reach Detection Band

Program

Terminal Settings

Output Terminals

Reach

Speed

Reach Detection Band

This parameter sets the bandwidth of the Speed Reach Frequency setting.

Parameter Type — Numerical

Factory Default — 2.5

Changeable During Run — Yes

Minimum — 0.0

Maximum — Max. Freq.

Units — Hz

Speed Reach Setting Frequency

Program

Output Terminals

Speed Reach Setting Frequency

This setting establishes a frequency threshold that, when reached or is within
the Reach Detection bandwidth, will provide a signal at an output terminal that
can close an appropriately configured output contact.

Parameter Type — Numerical

Factory Default — 2.5

Changeable During Run — Yes

Minimum — 0.0

Maximum — Max. Freq.

Units — Hz

Speed Reference Address

Program

Communication Settings

S20 Settings

The S20 system is Toshiba’s high-speed fiber optic communication system.
This function is unavailable at the time of this release.

Parameter Type — Selection List

Factory Default — 0

Changeable During Run — No

Speed Reference Station

Program

Communication Settings

S20 Settings

The S20 system is Toshiba’s high-speed fiber optic communication system.
This function is unavailable at the time of this release.

Parameter Type — Selection List

Factory Default — 0

Changeable During Run — No

Stall Prevention During Regeneration

Program

Protection Settings

Stall Prevention During

Regeneration

Enables/Disables the Overvoltage Stall and the Overcurrent Stall function
during regeneration only.

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Speed Drop Detection Frequency Range

Stall Prevention During Regeneration