W7 ASD Installation and Operation Manual

DC Injection on at Direction Change

Program

Protection Settings

DC Injection On Direction Change

Enable

This parameter Enables/Disables the use of DC Injection braking during a
change in the direction of the motor.

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

Deceleration Time #1

Program

Fundamental Parameters

Fundamental #1

Deceleration Time #1

This parameter specifies the time in seconds for the ASD output to go from the
Maximum Frequency to 0.0 Hz for the #1 Deceleration profile. The accel/
decel pattern may be set using Accel/Decel #1 Pattern.

Note: A deceleration time shorter than the load will allow may

cause nuisance tripping and mechanical stress to loads.

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Decel Time #2

Program

Fundamental Parameters

Fundamental #2

Deceleration Time #2

This parameter specifies the time in seconds for the ASD output to go from the
Maximum Frequency to 0.0 Hz for the #2 Deceleration profile. The accel/
decel pattern may be set using Accel/Decel #2 Pattern.

This setting is also used to determine the deceleration rate of the Motorized
Pot
function.

Note: A deceleration time shorter than the load will allow may

cause nuisance tripping and mechanical stress to loads.

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Delay Filter

Program

Feedback Settings

Delay Filter

This parameter determines the delay in the ASD output response to the motor-
control feedback signal.

Parameter Type — Numerical

Factory Default — 0

Changeable During Run — Yes

Minimum — 0

Maximum — 255

Differential (D) Gain

Program

Feedback Settings

Diff Gain

This parameter determines the degree that the differential function affects the
output signal. The larger the value entered here, the more pronounced the
Differential Gain.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 2.55

DC Injection on at Direction Change

Differential (D) Gain