Remote peripheral monitoring, Overview, Rpm modules – GE Industrial Solutions Galaxy Power Systems User Manual

Page 143: 10 remote peripheral monitoring, Overview 10-1, Table 10-a: rpm modules and connection units

Advertising
background image

Installation Guide for Galaxy Power Systems

Issue 12 August 2012

Remote Peripheral Monitoring 10 - 1

10

Remote Peripheral Monitoring

Overview

Note: The Remote Peripheral Monitoring feature is not available on
the Galaxy Vector Controller.

RPM Modules

The Remote Peripheral Monitoring measurement and control modules
provide data acquisition and control functions for a power environment.
System capacity is added in a modular fashion with measurement and
control modules. Each measurement module consists of six input
channels and one temperature channel. A temperature module has seven
channels to measure the temperature of seven different points in the
system. A control module provides three separate control relays. The
modules, which communicate back to the controller, are physically
connected in a daisy-chain bus configuration. The user can program
various alarm and control functions with the modules when used with a
Galaxy Millennium controller.

Table 10-A lists the RPM modules.

Table 10-A: RPM Modules and Connection Units

Module Type(s)

Module Code(s)

Module and Connection

Unit Kit Comcode

Control Relay

214A

108298456

Voltage (0-3Vdc)

221A

108298431

Voltage (0-16Vdc)

221B

108298498

Voltage (0-70Vdc)

221C

108469503

Voltage (0-200Vdc)

221D

108469479

Shunt

221F

108469461

Transducer

221J

108469495

Binary

222A

108298449

Temperature

223T

108274242