Installation Guide for Galaxy Power Systems

Issue 12 August 2012

Power Up and Installation Completion 15 - 13

Setting the System Float Voltage

Setting the System Float Voltage

Step

Action

1

Enter the appropriate key sequence:

• Millennium Controller:


Main

Config Rect Mngr Enter (Basic)

Main

Config Rect Mngr Rect Oper Enter

(Intelligent)

• Vector Controller:

Main

Configuration Float Voltages Set Point

2

Verify that the HFV, HVSD, and SHVSD alarm thresholds are
set above the float voltage to be specified in Step 3.

3

Use the adjust keys to set the system float voltage. In
Millennium, the STEP field may be adjusted to 1V, .0.1V, or
0.01V to establish the voltage increments that the ADJ keys
use when setting the system float voltage.