Setting the system float voltage – GE Industrial Solutions Galaxy Power Systems User Manual
Page 197
Advertising
Installation Guide for Galaxy Power Systems
Issue 12 August 2012
Power Up and Installation Completion 15 - 13
Setting the System Float Voltage
Setting the System Float Voltage
Step
Action
1
Enter the appropriate key sequence:
• Millennium Controller:
Main
Config Rect Mngr Enter (Basic)
Main
Config Rect Mngr Rect Oper Enter
(Intelligent)
• Vector Controller:
Main
Configuration Float Voltages Set Point
2
Verify that the HFV, HVSD, and SHVSD alarm thresholds are
set above the float voltage to be specified in Step 3.
3
Use the adjust keys to set the system float voltage. In
Millennium, the STEP field may be adjusted to 1V, .0.1V, or
0.01V to establish the voltage increments that the ADJ keys
use when setting the system float voltage.