Connecting batteries – GE Industrial Solutions Galaxy Power Systems User Manual

Page 203

Advertising
background image

Installation Guide for Galaxy Power Systems

Issue 12 August 2012

Power Up and Installation Completion 15 - 19

Connecting Batteries

Caution: Review and observe precautions outlined in Section 2,

Safety, before proceeding.

Connecting Batteries

Step

Action

1

Turn the system OFF. Turn the rectifiers to STBY. Open
the rectifier circuit breakers and system load circuit
breakers, if equipped.

2

Connect the batteries to the system. Choose the appropriate
method:

• Install the battery fuses and alarm fuses, or

• Close the battery circuit breakers, or

• Set the battery contactor board switches from forced open

to normal state, or

• Connect the remaining battery conductors. (See Figures

15-5 and 4-1 through 4-4.)

3

Turn the system ON. Turn ON all rectifiers. Close the
rectifier output circuit breakers (if equipped).

4

Observe that all rectifiers share the battery charging load
current. When this current stabilizes or drops to a level equal
to several amperes per string, proceed to the next section.