Ac input schemes, 596 rectifiers (24v, 100a/125a and 48v, 50a/100a) – GE Industrial Solutions Galaxy Power Systems User Manual

Page 87

Advertising
background image

Installation Guide for Galaxy Power Systems

Issue 12 August 2012

AC Connection and Wiring 7 - 3

AC Input Schemes

595 Rectifiers (48V,

200A) and 595LT

Rectifiers (48V,

220A)

595 and 595LT series rectifier input and output voltages are as shown
below.

Input

Rectifier

Output

380-480Vac, 3-phase, 50/60 Hz

595A and 595LTA series

48Vdc

200-240Vac, 3-phase, 50/60 Hz

595B and 595LTB series

The system supports three ac schemes:

Single bulk 3-wire (3-phase): The panel is factory equipped to
distribute the appropriate connections to the rectifiers through
circuit breakers.

Multiple bulk 3-wire (3-phase): The panel is factory equipped to
distribute the appropriate connections to the rectifiers through
circuit breakers.

Multiple 3-wire (3-phase): Connected directly to the terminal strips,
which then distribute the ac power to the rectifiers. One feed for
each rectifier, external circuit overload protection, must be
provided by customer.

596 Rectifiers (24V,

100A/125A and

48V, 50A/100A)

596 series rectifier input and output voltages are as shown below.

Input

Rectifier

Output

176-264Vac, 1-phase, 50/60 Hz

596A and D series

48Vdc

596B series

24Vdc

The ac power may be phase-to-phase or phase-to-neutral, as long as the
correct voltage range is provided to the rectifier.

The system supports two ac input schemes:

A single bulk 3-wire (3-phase) or 4-wire (3-phase + neutral) can be
brought into the ac panel located in the cabinet. The panel is factory
equipped to have either a phase-to-phase or phase-to-neutral
distribution to each rectifier through a two-pole ac circuit breaker.
Jumpers can be ordered to field modify the phase-to-phase panel to
have a phase-to-neutral distribution to each rectifier through a
two-pole ac circuit breaker.