Installation Guide for Galaxy Power Systems

Issue 12 August 2012

Addition or Modification to a Galaxy Power System 16 - 7

Replacing the Bay

Interface Card

(BIC) or BLJ3

Terminal Board

The BLJ3 Terminal Board, shown in Figure 16-3, provides a means to
connect all cabinet alarms and control signals in the cabinet. When the
cabinet is equipped with a Millennium controller, a Bay Interface Card
(BIC) is attached to the terminal board as shown in Figure 16-4. The
BIC is the interface between the BLJ3 terminal board and the
Millennium controller. It provides LVBD and LVLD control,
temperature probe inputs, alarm inputs, cabinet audible and visual
alarms and battery voltage and shunt measurement.

Figure 16-3: BLJ3 Terminal Board

Alarm Outputs

Contactors

Alarm Inputs

Battery Temperatures

Battery

Voltage

Bay

Alarm

Out

System

Shunt

Front Panel

Control/Display

To Rectifiers

Power In/Out

Battery Shunts

Vector Controller

Board Not Shown

26 Conductor
Ribbon Cable

Fuses

BIC

System Configuration

DIP Switches