Millennium controller – GE Industrial Solutions Galaxy Power Systems User Manual

Page 79

Advertising
background image

Installation Guide for Galaxy Power Systems

Issue 12 August 2012

Centralized or Distributed Architecture Connections 6 - 11

Intercabinet Alarm and Serial Bus Connections, continued

BLJ2/3 to BLJ2/3

(Millennium

Controller),

continued

BLJ2/3 to BLJ2/3 (Millennium Controller), continued

Step

Action

2

Set the DIP switch on the BLJ2/3 board for the bay ID number.
(Factory default is Bay 1.)

S1.1 - S1.3: Bay ID

S1.4, S1.5, S1.6: Shunt Size*

S1.7, S1.8: Bay ID

0

1

0
0
1
1
0
0
1
1

0
0
0
0
1
1
1
1

0
1
0
1
0
1
0
1

1000

600
150

1500
2000
3000

Invalid

User-Defined

(shown)

S1.1

0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1

S1.2

0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1

S1.7

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

S1.3

0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

S1.8

0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1

1
2
3
4
5
6
7
8
9

10

11

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

(shown)

*Shunt size settings for distributed

architecture only.

Bay ID

Shunt Size (Amps)*

S1.4

S1.5

S1.6

Figure 6-6: BLJ2/3 DIP Switch Settings When Using a

Millennium Controller