Page 79
Installation Guide for Galaxy Power Systems
Issue 12 August 2012
Centralized or Distributed Architecture Connections 6 - 11
Intercabinet Alarm and Serial Bus Connections, continued
BLJ2/3 to BLJ2/3
(Millennium
Controller),
continued
BLJ2/3 to BLJ2/3 (Millennium Controller), continued
Step
Action
2
Set the DIP switch on the BLJ2/3 board for the bay ID number.
(Factory default is Bay 1.)
S1.1 - S1.3: Bay ID
S1.4, S1.5, S1.6: Shunt Size*
S1.7, S1.8: Bay ID
0
1
0
0
1
1
0
0
1
1
0
0
0
0
1
1
1
1
0
1
0
1
0
1
0
1
1000
600
150
1500
2000
3000
Invalid
User-Defined
(shown)
S1.1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
S1.2
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
S1.7
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
S1.3
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
S1.8
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
(shown)
*Shunt size settings for distributed
architecture only.
Bay ID
Shunt Size (Amps)*
S1.4
S1.5
S1.6
Figure 6-6: BLJ2/3 DIP Switch Settings When Using a
Millennium Controller