Installing an lvld contactor (if required) – GE Industrial Solutions Galaxy Power Systems User Manual

Page 215

Advertising
background image

Installation Guide for Galaxy Power Systems

Issue 12 August 2012

Addition or Modification to a Galaxy Power System 16 - 5

Installing an LVLD Contactor (if required)

Figure 16-2: Adding an LVLD to a Distribution Panel

1

2

3

Cabinet (REF)

1. Attach the LVLD control board to the cabinet as shown using two

M5 screws. Torque to 30 in·lbs.

2. Connect the contactor between the panel and the L-shaped bus

using four M8 screws, lockwashers and washers. Torque to 120
in·lbs.

3. Connect the 847992184 wireset (48V systems) or the 848110995

wireset (24V systems) from the LVLD control board to the
contactor. Refer to wiring diagram T-83314-30 sheet B87 for
connections.