Installation Guide for Galaxy Power Systems

15 - 22 Power Up and Installation Completion

Issue 12 August 2012

Testing Temperature Compensation (Optional Feature)

Testing Temperature Compensation (Optional)

Step

Action

1

Enter the appropriate key sequence:

• Galaxy Millennium Controller:


Main

Config Bat Mngr STC Enter

• Galaxy Vector Controller:

Main

Configuration Batteries Batt Temp

Management

Temp Compensation Temp Comp

2

Enable the slope thermal compensation feature, if installed.

3

Verify that the battery temperature threshold configurations
are set to values that produce a compensation slope that is
correct for the battery type being used. The Nominal, Upper,
and Step temperature settings of Millennium software
versions earlier than 7.5 will need to be adjusted from their
default values when Temperature Compensation is enabled,
or battery damage may result.

4

If thermal probes are installed, heat one of the probes to
simulate a battery operating at high temperature.

5

Verify that the system voltage is reduced from the nominal
float voltage value as the thermal probe is heated.

6

Allow the thermal probe to cool and verify that the system
voltage returns to the nominal value.