Installation Guide for Galaxy Power Systems

7 - 4 AC Connection and Wiring

Issue 12 August 2012

A 2-wire (phase-to-phase or phase-to-neutral) feed for each rectifier
is brought into a terminal strip located in the cabinet. The terminal
strip provides distribution to each rectifier. External circuit
overload protection must be provided by the customer.

Note: All wire sizes are based on the US National Electric Code.

AC Cable Routing

Caution: Follow all local codes and practices when performing the steps
to connect ac to the power system.

AC Cable Routing

Step

Action

1

Clearly label the main ac circuit breaker panel, stating that
installers are working in the ac cabling.

2

Check that all ac circuit breakers are turned OFF.

3

Route the ac cables to the cabinet as required by local
building codes.

4

At the cabinet, route the ac cables through the access hole(s)
in the top of the cabinet.

5

Install terminal lugs (if applicable) to cables.