Installation Guide for Galaxy Power Systems

15 - 18 Power Up and Installation Completion

Issue 12 August 2012

Setting the Low-Voltage Load Disconnect Feature, continued

Setting the LVLD Feature, continued

Step

Action

2

The default thresholds are:

• Galaxy Millennium Controller:


disconnect voltage:

+22V (for +24V systems) or -44V (for -48V systems)


reconnect voltage:

+24V (for +24V systems) or -48V (for -48V systems)

• Galaxy Vector Controller:

disconnect voltage:

+21V (for +24V systems) or -43.20V (for -48V systems)


reconnect voltage:

+22.20V (for +24V systems) or -44.40V (for -48V systems)

To set the thresholds to other values, enter the appropriate key
sequence:

• Galaxy Millennium Controller:


Main

Config LVD (Basic) or Low V Disc (Intelligent)

Contactor 2 Type-Load Change Thresholds
Enter

• Galaxy Vector Controller:

Main

Configuration Contactors Contactor 2

Disconnect/Reconnect

Save

Note: The factory default for all load disconnect contactors in the
system is hardwired as Contactor 2. In a Millennium system this
can be changed to Contactor 3 to allow some load contactors to
open at different thresholds. To change, move the jumpers on the
associated EBV contactor drive boards as shown in Figure 8-13.
Then set Millennium’s Contactor 3 configuration to Load with the
desired thresholds as described above.