GE Industrial Solutions Galaxy Power Systems User Manual

Page 200

Advertising
background image

Installation Guide for Galaxy Power Systems

15 - 16 Power Up and Installation Completion

Issue 12 August 2012

Setting the Low-Voltage Battery Disconnect Feature, continued

Setting the LVBD Feature, continued

Step

Action

2

The default thresholds are:

• Galaxy Millennium Controller:


disconnect voltage:

+22V (for +24V systems) or -44V (for -48V systems)


reconnect voltage:

+24V (for +24V systems) or -48V (for -48V systems)

• Galaxy Vector Controller:

disconnect voltage:

+21V (for +24V systems) or -43.20V (for -48V systems)


reconnect voltage:

+22.20V (for +24V systems) or -44.40V (for -48V
systems)

To set the thresholds to other values, enter the appropriate
key sequence:

• Galaxy Millennium Controller:


Main

Config LVD (Basic) or Low V Disc

(Intelligent)

Contactor 1 Type-Battery

Change Thresholds

Enter

• Galaxy Vector Controller:

Main

Configuration Contactors Contactor 1

Disconnect/Reconnect Save

Note: The factory default on all battery contactors in the
system is hardwired as Contactor 1. This cannot be changed.