Figure 6-8: blj3 dip switch settings when using a, Vectorcontroller, Blj3 to blj3 (vector controller), continued – GE Industrial Solutions Galaxy Power Systems User Manual

Page 82

Advertising
background image

Installation Guide for Galaxy Power Systems

6 - 14 Centralized or Distributed Architecture Connections

Issue 12 August 2012

Intercabinet Alarm and Serial Bus Connections, continued

BLJ3 to BLJ3

(Vector Controller),

continued

BLJ3 to BLJ3 (Vector Controller), continued

Step

Action

5

Set the DIP switch on the BLJ3 board. (Factory default for DIP switches is 0.)

Alarm Outputs

Fuses

Contactors

Alarm Inputs

Thermal Inputs

Plant Voltage

Regulation Input

Bay

Alarm Out

Unused

Unused

Unused

Unused

To Modem/

Gateway/

Local Terminal

Front Panel

Control/Display

To Rectifiers

Power In/Out

Shunts 1 and 2

Unused

Vector Controller

Board Not Shown

26 Conductor
Ribbon Cable

Vector Controller Board

(GCM2, GCM3)

System Configuration

DIP Switches

0

1

1

S1

2

3 4

5

6 7

8

S1.2: Software Mode

1,2

S1.3: Option Card Availability

S1.5: Alarm Contact Select

1

S1.7: Power Battery Test

S1.1: Front Panel Configuration

0
1

0
1

0
1

0
1

0
1

- Enabled (shown)
- Disabled

- Standard (shown)
- Flexent System Only

- Modem
- Galaxy Gateway Card (Internet)

S1.4: Rectifier Class

0
1

- Standard GPS Rectifiers
- NP Rectifiers

- Standard HV, High Voltage
- VLV, Very Low Voltage

- Disabled (shown)
- Active

S1.6: - Set to 0

S1.8: - Set to 0

1. Setting both SW1.2 and SW1.5 to "1" will result in activating the HV alarm cont act.
2. SW1.2 setting will only be read by the software when the GCM is powered up.

Figure 6-8: BLJ3 DIP Switch Settings When Using a

VectorController