Mounting specifications, Table 5-b: gps mounting specifications, Cabinet installation, continued – GE Industrial Solutions Galaxy Power Systems User Manual
Page 60
Installation Guide for Galaxy Power Systems
5 - 14 Cabinet Floor Mounting and Battery Stand Connection
Issue 12 August 2012
Cabinet Installation, continued
Mounting
Specifications
Table 5-B: GPS Mounting Specifications
Seismic
Zone(s)
Comcode
Anchor Type
(HILTI)
Hole Size
Wrench
Torque
0, 1
847135720
(4) 3/8"
drop in
1/2" bit
1-9/16" deep
--
85 in·lbs
(7.1 ft·lbs)
9.6 N·m
0, 1
847135712
(4) 3/8"
self drill
--
--
85 in·lbs
(7.1 ft·lbs)
9.6 N·m
0, 1, 2
847135662
(4) 1/2"
drop-in
5/8" bit
2" deep
3/4"
216 in·lbs
(18 ft·lbs)
24.5 N·m
0, 1, 2
847135654
(4) 1/2"
self drill
--
3/4"
216 in·lbs
(18 ft·lbs)
24.5 N·m
0, 1, 2, 3, 4 847135670
(4) 12mm
self drill
--
19mm
720 in·lbs
(60 ft·lbs)
81.6 N·m
0, 1, 2, 3, 4 847135688
(4) 12mm
cap bolts
18mm
100mm deep
19mm
720 in·lbs
(60 ft·lbs)
81.6 N·m
4*
847221074
(4) 16mm
cap bolts
24mm
125mm deep
30mm
1800 in·lbs
(150 ft·lbs)
204 N·m
*IR Battery Stand only