5 - 14 Cabinet Floor Mounting and Battery Stand Connection

Issue 12 August 2012

Cabinet Installation, continued

Mounting

Specifications

Table 5-B: GPS Mounting Specifications

Seismic
Zone(s)

Comcode

Anchor Type

(HILTI)

Hole Size

Wrench

Torque

0, 1

847135720

(4) 3/8"

drop in

1/2" bit

1-9/16" deep

--

85 in·lbs

(7.1 ft·lbs)

9.6 N·m

0, 1

847135712

(4) 3/8"

self drill

--

--

85 in·lbs

(7.1 ft·lbs)

9.6 N·m

0, 1, 2

847135662

(4) 1/2"

drop-in

5/8" bit

2" deep

3/4"

216 in·lbs
(18 ft·lbs)

24.5 N·m

0, 1, 2

847135654

(4) 1/2"

self drill

--

3/4"

216 in·lbs
(18 ft·lbs)

24.5 N·m

0, 1, 2, 3, 4 847135670

(4) 12mm

self drill

--

19mm

720 in·lbs
(60 ft·lbs)

81.6 N·m

0, 1, 2, 3, 4 847135688

(4) 12mm

cap bolts

18mm

100mm deep

19mm

720 in·lbs
(60 ft·lbs)

81.6 N·m

4*

847221074

(4) 16mm

cap bolts

24mm

125mm deep

30mm

1800 in·lbs
(150 ft·lbs)

204 N·m