Installation Guide for Galaxy Power Systems

2 - 6 Safety

Issue 12 August 2012

Precautions, continued

Note: Provide cable run lengths as least as long as the minimum length
indicated in Table 2-A to assure that the short circuit currents are less
than the interrupt current rating of the fuse or circuit breaker chosen.

1. Find the interrupt current rating of the chosen fuse or circuit

breaker from Table 2-B.

2. See Table 2-A for the minimum length (L) for the engineered cable

size to be run at the interrupt rating found in Step 1.

A minimum cable length for a given cable size and protector type must
be used to ensure proper short circuit protection in the case of a bolted
fault.

Table 2-A: Cable Run Lengths

Cable Size

Minimum Length “L” Required to Limit the Current to an

Interrupt Rating of:

100KA

25KA

10KA

10 GA

(6mm

2

)

--

--

5 feet

8 GA

(10 mm

2

)

--

--

8 feet

6 GA

(16 mm

2

)

--

5 feet

12 feet

4 GA

(25 mm

2

)

--

8 feet

19 feet

2 GA

(35 mm

2

)

3 feet

12 feet

30 feet

1/0 GA

(50 mm

2

)

5 feet

19 feet

--

2/0 GA

(70 mm

2

)

6 feet

24 feet

--

4/0 GA

(120 mm

2

)

10 feet

38 feet

--

(2) 4/0 GA

((2) 120 mm

2

)

19 feet

76 feet

--

(3) 4/0 GA

((3) 120 mm

2

)

29 feet

113 feet

--

350 MCM

17 feet

63 feet

--

(2) 350 MCM

32 feet

125 feet

--

(3) 350 MCM

47 feet

188 feet

--