Current limiting resistors, Mounting locations, Figure 10-1: possible rpm mounting locations – GE Industrial Solutions Galaxy Power Systems User Manual

Page 144: Overview, continued

Advertising
background image

Installation Guide for Galaxy Power Systems

10 - 2 Remote Peripheral Monitoring

Issue 12 August 2012

Overview, continued

Current Limiting

Resistors

Current limiting resistors (100K-ohm) are required for the measurement
inputs of the voltage, current, and binary modules. Comcode 847540424
current limiting resistor assemblies are available for connections that do
not already have them. All shunts (load and battery) and some voltage
points that are provided with the GPS cabinet already have current
limiting resistors; check T-83314-30 for resistor presence.

For the 214A Control Relay module, the maximum relay contact voltage
is 110Vdc and maximum current is 0.3Adc. Wiring depends on the
voltage, current, local building codes, and various other characteristics
of the controlled point.

Mounting

Locations

Figure 10-1 shows possible mounting locations for the RPMs.

Figure 10-1: Possible RPM Mounting Locations

Part of Module Kit

Modules can also be mounted on blank 6", 9", and 12"
panels inside the cabinet (H569-434/H569-436/H569-437
G90, G91, and G92).

Panel
848535332

Panel
848412367
(Provided with H569-434 G28 and G29
1200A and 4800A Distribution Only Cabinets)

6-32 Nut
901233502

10-32x7/16" Screw
901252726

10-32x7/16" Screw
901252726

Advertising