Centralized architecture, continued – GE Industrial Solutions Galaxy Power Systems User Manual

Page 71

Advertising
background image

Installation Guide for Galaxy Power Systems

Issue 12 August 2012

Centralized or Distributed Architecture Connections 6 - 3

To Centralized Charge
Ground Bus Bar

Torque: 300 in-lbs (34 Nm)

To Centralized
Charge Battery Bus Bar

Rectifier Output
Negative for 48V systems
Positive for 24V systems

Return
Positive for 48V systems
Negative for 24V systems

Bat/Rtn
Bat/Rtn
Bat/Rtn
Bat/Rtn
Bat/Rtn
Bat/Rtn
Bat/Rtn
Bat/Rtn
Bat/Rtn
Bat/Rtn
Bat/Rtn

1/0
2/0

--

4/0

--

350

--

500

--

750

--

--

1/0
2/0

--

4/0

--

350

--

500

--

750

50
70

--
--

120

--
--
--
--
--
--

847867132

(One or two

required per
connection.)

Lugs and Hardware

Type Std Wire Ga

(Class B)

Metric

Wire Size

(mm )

2

Hardware Kit

(Grade 2)

Flex Wire Ga

(Class I)

Lug

Comcode

405348228
405348236
406021725
405348251
405347923
407890763
407890748
407850833
407890755
406335141
407890730

Optional Rectifier Output Bus Bars
848285847
(GPS4848/100 only)
Torque: 300 in-lbs (34 Nm)

(Note)

Note: Limited to 4 terminations maximum per bus or 8 maximum
(back-to-back) per 848285847 extension bus bar.

To Centralized
Charge Battery Bus Bar

Rectifier Output
Negative for 48V systems
Positive for 24V systems

Centralized Architecture, continued

Figure 6-1: DC Power Connections to Centralized Bus Bars