Testing rectifiers and load share – GE Industrial Solutions Galaxy Power Systems User Manual

Page 205

Advertising
background image

Installation Guide for Galaxy Power Systems

Issue 12 August 2012

Power Up and Installation Completion 15 - 21

Testing Rectifiers and Load Share

Testing Rectifiers and Load Share

Step

Action

1

Turn all rectifiers to STBY.

2

Connect a resistive load box (proper voltage) to the system’s
positive and negative bus bars.

3

Verify that the system load is less than 50 amperes.

4

Increase the system load to 50 amperes.

5

Turn ON all the rectifiers; after approximately 60 seconds,
verify that the load is divided equally among all the rectifiers
(within 2 amperes).

6

Reduce the system load. Verify that the rectifiers continue to
share the load.

7

Remove system load.