7 - 2 AC Connection and Wiring

Issue 12 August 2012

Wire Sizing and Ampacity

Table 7-A: Wire Sizing and Ampacity

Standard Ga

Metric (mm

2

)

NEC Table 310-16

75°C (A) (see Note)

10

6

35

8

10

50

6

16

65

4

25

85

2

35

115

1/0

50

150

2/0

70

175

4/0

120

230

Note: For NEC code compliance, all wire sizing calculations are made assuming
75°C rated wire. Lineage Power recommends the use of 90°C rated wire, which
has a higher current carrying capacity, for all ac connections.

Figure 7-15

ED83142-30 Group 18 (H569-434 G128, G129, G130, G131,
G224, G226, G330, G331) AC Input Panel for 595A or 595B
Series Rectifiers

Figure 7-16

ED83142-30 Group 26 (H569-434 G328, G329, G332, G131,
G333) AC Input Panel for 595LTA or 595LTB Series Rectifiers

Figure 7-17

ED83142-30 Group 19 (H569-436 G172F) AC Input Panel for
596D Series Rectifiers

Figure 7-18

ED83142-30 Group 20, 22 (H569-436 G175H, G176H, G177F,
G178F, G179F) AC Input Panel for 596D Series Rectifiers

Figure 7-19

ED83142-30 Group 21 (H569-436 G171H) AC Input Panel for
596D series Rectifiers

Figure 7-20

ED83142-30 Group 23 (H569-436 G173F) AC Input Panel for
596D Series Rectifiers

Figure 7-21

Neutral AC Input for ED83142-30 G6, G7, G19, G21 or G23
H569-436 G71H, G72F, G73F, G171H, G172F, G173F; H569-437
G71H, 72F, or G73F

Figure 7-22

Bottom Cable Feed Option for GPS4848/100

Advertising