Installation Guide for Galaxy Power Systems

6 - 10 Centralized or Distributed Architecture Connections

Issue 12 August 2012

Intercabinet Alarm and Serial Bus Connections

BLJ2/3 to BLJ2/3

(Millennium

Controller)

The cable used in this procedure is:

Rectifier Interface Cable Assembly 847690799 (10 feet)

(provided with cabinet)

BLJ2/3 to BLJ2/3 (Millennium Controller)

Step

Action

1

Connect the Rectifier Interface Cable Assembly from J5 of one
BLJ2/3 board to J6 of the BLJ2/3 board in the next cabinet.

Note: Remove and discard any resistors that are blocking
access to J6 or J5 connection points, except for those in J5 of
the last cabinet.

J6

J7

J6

J7

J5

J5

Millennium

Controller

BLJ2/3
1st Cabinet

BLJ2/3
2nd Cabinet

Rectifier Interface Cable Assembly

Leave Resistor In
Place If Last Cabinet

or

Remove Resistor and
Connect to J6 of Next
Cabinet

To Rectifiers

in This Cabinet

To Rectifiers

in This Cabinet

To Next Cabinet
As Required

Factory Installed

Figure 6-5: BLJ2 or BLJ3 Board Connections,

Millennium Controller