Operations Manual

Series 3

18

4.4

Front Panel Layout

ALM Alarm active (Red)
OP1 lit when output 1 is ON
OP2 lit when output 2 is ON
OP3 lit when output 3 is ON
OP4 lit when output 4 relay is ON
SPX Alternative setpoint in use (e.g. setpoint 2)
REM Remote digital setpoint. Also flashes when digital
communications active
MAN Manual mode selected
Operator Buttons:

Referred to as the ‘page’ button. From any view -

press to return to the HOME display

Referred to as the ‘scroll’ button. Press to select a new

parameter. If held down it will continuously scroll through
parameters.

Press

and

(ACK) together to acknowledge an alarm.

Referred to as the ‘arrow down’ button. Press to

decrease a value

Referred to as the ‘arrow up’ button. Press to increase

a value

Press

and

(MODE) together to toggle between Auto

and Manual mode.
























4.4.1 To Set The Target Temperature.

From the HOME display:

Press

to raise the setpoint

Press

to lower the setpoint

The new setpoint is entered when the button is released
and is indicated by a brief flash of display.

4.4.2

Alarms

Process alarms may be configured using the Quick Start
Codes. Each alarm can be configured for:

Full Scale Low

The alarm is shown if the process value falls below a
set threshold

Full Scale High

The alarm is shown if the process value rises above a
set threshold

Deviation Low

The alarm is shown if the process value deviates below
the setpoint by a set threshold

Deviation High

The alarm is shown if the process value deviates above
the setpoint by a set threshold

Deviation Band

The alarm is shown if the process value deviates above

or

below the setpoint by a set threshold

If an alarm is not configured it is not shown in the list of
level 2 parameters.
Additional alarm messages may be shown such as
CONTROL LOOP BROKEN. This occurs if the controller
does not detect a change in process value following a
change in output demand after a suitable delay time.
Another alarm message may be INPUT SENSOR BROKEN
(SBr). This occurs if the sensor becomes open circuit; the
output level will adopt a ‘SAFE’ value which can be set up in
Operator Level 3..

From firmware version 2.11 two further alarm types

have been made available. These are:

Rising rate of
change

An alarm will be detected if the rate of change
(units/minute) in a positive direction exceeds the alarm
threshold

Falling rate of
change

An alarm will be detected if the rate of change
(units/minute) in a negative direction exceeds the alarm
threshold

These alarms cannot be configured by the Quick Start Code
– they can only be configured in Configuration Mode..

4.4.3

Alarm Indication

If an alarm occurs, the red ALM beacon will flash. A
scrolling text message will describe the source of the alarm.
Any output (usually a relay) attached to the alarm will
operate. An alarm relay can be configured using the Quick
Start Codes to be energised or de-energised in the alarm
condition. It is normal to configure the relay to be de-
energised in alarm so that an alarm is indicated if power to
the controller fails.

Press

and

(ACK) together to acknowledge an alarm.

If the alarm is still present the ALM beacon will light
continuously otherwise it will go off.
The action which takes place depends on the type of alarm
configured: