Super Systems 3 Series User Manual

Page 74

Advertising
background image

Operations Manual

Series 3

74

Parameter
Mnemonic

Parameter Name

Modbus Address

Decimal

Remote setpoint in percent

277

REM.HI

Remote input high scalar – sets high range for setpoint input, corresponding to 20mA or 10V depending on the input type.

278

REM.LO

Remote input low scalar – sets low range for setpoint input, corresponding to 4mA or 0V depending on the input type.

279

ROP.HI

Sets the high range limit for the retransmitted setpoint. Allows a subset of the setpoint range to be retransmitted, and also
allows the setpoint range meter to display a range indication other than full scale. By default this is set to the setpoint high
limit.

280

ROP.LO

Sets the low range limit for the retransmitted setpoint. Allows a subset of the setpoint range to be retransmitted, and also
allows the Series 3 setpoint range meter to display a range indication other than full scale. By default this is set to the setpoint
low limit.

281

A1.STS

Alarm 1 Status (0 = Off, 1 = Active)

294

A2.STS

Alarm 2 Status (0 = Off, 1 = Active)

295

A3.STS

Alarm 3 Status (0 = Off, 1 = Active)

296

A4.STS

Alarm 4 Status (0 = Off, 1 = Active)

297

LD.ALM

Low Load Current Threshold

304

LK.ALM

High Leakage Current Alarm (0 = Off, 1 = Active)

305

HC.ALM

Over Current Alarm Threshold

306

LOAD.A

Load Alarm Status (0 = Off, 1 = Active)

307

LEAK.A

Leak alarm Status.

308

HILC.A

Over Current alarm Status (0 = Off, 1 = Active)

309

REC.NO

FEATURE NOT AVAILABLE

313

StOrE

FEATURE NOT AVAILABLE

314

TM.CFG

FEATURE NOT AVAILABLE

320

TM.RES

FEATURE NOT AVAILABLE

321

SS.SP

Soft Start Setpoint

322

SS.PWR

Soft Start Power Limit

323

DWELL

FEATURE NOT AVAILABLE

324

T.ELAP

FEATURE NOT AVAILABLE

325

T.REMN

FEATURE NOT AVAILABLE

326

THRES

FEATURE NOT AVAILABLE

327

End.T

FEATURE NOT AVAILABLE

328

SERVO

FEATURE UNAVAILABLE

329

EVENT

FEATURE NOT AVAILABLE

331

P.CYCL

FEATURE NOT AVAILABLE

332

CYCLE

FEATURE NOT AVAILABLE

333

CTRL.H

Heat/Ch1 Control Type
0 – Off
1 – On/Off Control
2 – PID Control
3 – mtr Valve Position Control

512

CTRL.C

Cool/Ch2 Control Type
0 – Off
1 – On/Off Control
2 – PID Control

513

PB.UNT

Proportional Band Units
0 – Engineering Units
1 – Percent of Span

514

Lev2.P

Level 2 Code

515

UNITS

Display Units
0 – Degrees C
1 – Degrees F
2 – Kelvin
3 – None
4 – Percent

516

Lev3.P

Level 3 Code

517

Conf.P

Config Code

518

Cold

If set to 1 instrument will reset to factory defaults on next reset or power cycle.

519

PASS.C

Feature passcode C

520

PASS.2

Feature passcode 2

521

COOL.t

Cooling Algorithm Type:

524