Super Systems 3 Series User Manual

Page 75

Advertising
background image

Series 3

Operations Manual

75

Parameter
Mnemonic

Parameter Name

Modbus Address

Decimal

0 – Linear
1 – Oil
2 – Water
3 – Fan

DEC.P

Decimal Point Position
0 – XXXX.
1 – XXX.X
2 – XX.XX

525

STBY.T

Standby Type
0 – Absolute Alarm Outputs Active – others off
1 – All outputs inactive

530

RAMP
UNITS

0 – Ramp per Minute
1 – Ramp per Hour
2 – Ramp per Second

531

Meter

Ammeter configuration
0 – No ammeter
1 – Heat Output (0-100%)
2 – Cool Output (0-100% cooling)
3 – Working Setpoint (scaled within SP limits)
4 – PV (scaled within range)
5 – Output Power (scaled within Op Low and OP High limits)
6 – Output centered between –100% and 100%
7 – Error (PV-SP) (scaled between +/- 10 degrees)
8 – Instantaneous Amps (scaled 0 to CT Span)
9 – Load Current (scaled 0 to CT Span)

532

uCAL

User Calibration Enable

533

A1.TYP





Alarm 1 Type
0 – Off
1 –Absolute High
2 – Absolute Low
3 – Deviation High
4 – Deviation Low
5 – Deviation Band

536





A2.TYP

Alarm 2 Type
(as Alarm 1 Type)

537

A3.TYP

Alarm 3 Type
(as Alarm 1 Type)

538

A4.TYP

Alarm 4 Type
(as Alarm 1 Type)

539

A1.LAT


Alarm 1 Latching Mode
0 – No latching
1 – Latch - Automatic Reset
2 – Latch – Manual Reset

540


A2.LAT

Alarm 2 Latching Mode
(as Alarm 1 Latching Mode)

541

A3.LAT

Alarm 3 Latching Mode
(as Alarm 1 Latching Mode)

542

A4.LAT

Alarm 4 Latching Mode
(as Alarm 1 Latching Mode)

543

A1.BLK

Alarm Blocking Mode Enable (0 = OFF, 1 = BLOCK)

544

A2.BLK

Alarm Blocking Mode Enable (0 = OFF, 1 = BLOCK)

545

A3.BLK

Alarm Blocking Mode Enable (0 = OFF, 1 = BLOCK)

546

A4.BLK

Alarm Blocking Mode Enable (0 = OFF, 1 = BLOCK)

547

Di.OP






Digital Outputs Status. This is a bitmap:
B0 – Output 1A
B1 – Output 2A
B3 – Output 4/AA
It is possible to write to this status word to use the digital outputs in a telemetry output mode. Only outputs whose function is
set to ‘none’ are affected, and the setting of any bits in the Digital Output Status word will not affect outputs used for heat (for
example) or other functions. Thus it is not necessary to mask in the settings of these bits when writing to this variable.

551






OFS.HI

Adjust High Offset

560

OFS.LO

Adjust Low Offset

561

PNT.HI

Adjust High Point

562