1 input types and ranges, Input types and ranges, N 8.1.1 – Super Systems 3 Series User Manual

Page 33

Advertising
background image

Series 3

Operations Manual

33

INPUT LIST

I N P U T

Name

Scrolling Display

Parameter Description

Value

Default

Access Level

R c . f t

ROC FILTER TIME

This provides a first order filter for
the rate of change filtering function
and can be used to avoid nuisance
alarm triggers due to short duration
noise on the calculated rate of
change,

oFF

to 0.1 to 999.9 minutes

Off means no filtering applied

1.6

L3

R C . P V

PV DERIVATIVE

Provides a measure of the calculated
rate of change of the temperature or
measurement input as used by the
Rate of Change Alarm functions.
Useful when commissioning to
determine the level of filtering
required on the Rate of Change
alarm.

L3

8.1.1

Input Types and Ranges

Input Type

Min Range

Max Range

Units

Min Range

Max Range

Units

J.tc

Thermocouple type J

-210

1200

o

-346

C

2192

o

F

k.tc

Thermocouple type K

-200

1372

o

-328

C

2502

o

F

L.tc

Thermocouple type L

-200

900

o

-328

C

1652

o

F

r.tc

Thermocouple type R

-50

1700

o

-58

C

3092

o

F

b.tc

Thermocouple type B

0

1820

o

32

C

3308

o

F

n.tc

Thermocouple type N

-200

1300

o

-328

C

2372

o

F

t.tc

Thermocouple type T

-200

400

o

-328

C

752

o

F

S.tc

Thermocouple type S

-50

1768

o

-58

C

3215

o

F

Rtd

Pt100 resistance thermometer

-200

850

o

-328

C

1562

o

F

mv

mV or mA linear input

-10.00

80.00

Cms

Value received over digital
communications (modbus address
203).
This value must be updated every 5
seconds or the controller will show
sensor break