9 aa relay (aa) (output 4), Aa relay (aa) (output 4) – Super Systems 3 Series User Manual

Page 40

Advertising
background image

Operations Manual

Series 3

40

9.1.9

AA Relay (AA) (Output 4)

This is a changeover relay. Connections are made to terminals AA, AB, and AC. The way in which this relay operates is
determined by parameters in the AA List. OP4 beacon is operated from the AA relay output channel.

AA RELAY ‘aa’

Name

Scrolling

Display

Parameter Description

Value

Default

Access Level

4.TYPE

OUTPUT 4
TYPE

Output channel 4 hardware
type

reLy

Relay output

reLy

Read only

4.FUNC

FUNCTION

Output channel 4 function
If the instrument is ordered as
Valve Position (codes VC or
VP), only values none, d.out,
UP,

or dwn are available

Note: If output 4 is set to up
ensure the other valve
position output is set to dwn
and vice versa

none

Disabled

d.OUt

Conf

d.OUt

Digital output

Heat

Heat output

CooL

Cool output

4.SRC.A

I/O 4 SOURCE A

These parameters only appear
when the channel function is a
Digital OP,
i.e. 4.FUNC = d.Out

Selects an event status to be
connected to the output
channel.

The output status is the result
of an OR of Src A, Src B, Src C,
and Src D

Up to four events can,
therefore, operate the output

none

No event connected to the output

none

Conf

AL1

Alarm 1 *

4.SRC.B

I/O 4 SOURCE B

AL2

Alarm 2 *

AL3

Alarm 3 *

4.SRC.C

I/O 4 SOURCE C

AL4

Alarm4 *

ALL.A

All alarms

4.SRC.D

I/O 4 SOURCE D

nw.AL

Any new alarm

Ct.AL

CT alarm, load, leak & overcurrent

Lbr

Loop break alarm

Sbr

Sensor break alarm

mAn

Manual status

rmt.F

Remote fail

Pwr.f

Power fail

prg.e

FEATURE UNAVAILABLE

4.SENS

SENSE

To configure the polarity of
output channel 4

nor

Normal

nor

Conf

Inv

Inverted


* The mnemonic for the alarm will change depending upon the alarm configuration.