Series 3

Operations Manual

73

Parameter
Mnemonic

Parameter Name

Modbus Address

Decimal

-

Inverted Instrument Status. This is an inverted (bitwise) version of the preceding parameter and is provided so that scrolling
messages can be triggered when a condition is not active. Bit mappings are as the “Instrument Status”, Modbus address 75

76

LL.AMP

Load Leakage Current

79

LD.AMP

Load ON Current

80

A3.---

Alarm 3 Threshold

81

A4.---

Alarm 4 Threshold

82

LBT

Loop Break Time

83

F.OP

Forced manual output value

84

F.MOD

Forced manual output mode
0 – None
1 - Step
2 - Last

85

HYST.H

Ch1 On/Off Hysteresis in Eng Units

86

Di.IP

Digital Inputs Status. This is a bitmap:
B0 – Logic input 1A
B1 – Logic input LA
B2 – Logic input LB
B7 – Power has failed since last alarm acknowledge
A value of 1 signifies the input is closed, otherwise it is zero. Values are undefined if options are not fitted or not configured as
inputs.

87

HYST.C

Ch2 On/Off Hysteresis in Eng Units

88

FILT.T

Input Filter Time

101

RC.FT

Filter time constant for the rate of change alarm.

102

RC.PV

Calculated rate of change of the temperature or process variable in engineering units per minute.

103

Home

Home Display.
0 – Standard PV and SP display
1 – PV and Output Power display
2 – PV and Time remaining display
3 – PV
4 – FEATURE NOT AVAILABLE
5 – PV and Load Current
6 – PV only
7 – PV and Composite SP/Time remaining
8 – Target setpoint
9 – No PV
10 – PV is not displayed when controller in Standby

106

-

Instrument version number. Should be read as a hexadecimal number, for example a value of 0111 hex is instrument V1.11

107

SP.HI

Setpoint High Limit

111

SP.LO

Setpoint Low Limit

112

-

Instrument type code.

122

ADDR

Instrument Comms Address

131

PV.OFS

PV Offset

141

C.Adj

Calibration Adjust

146

IM

Instrument Mode
0 – Operating mode - all algorithms and I/O are active
1 – Standby - control outputs are off
2 – Config Mode - all outputs are inactive

199

MV.IN

Input value in millivolts

202

PV.CM

Comms PV Value. This may be used to write to the Process Variable (temperature) parameter over Modbus when a
linearisation type of ‘Comms’ is selected, allowing the instrument to control to externally derived values.
If sensor break is turned on, it is necessary to write to this variable once every 5 seconds. Otherwise a sensor break alarm will be
triggered as a failsafe. If this is not required, turn sensor break off.

203

CJC.IN

CJC Temperature

215

SBR

Sensor Break Status (0 = Off, 1 = Active)

258

NEW.AL

New Alarm Status (0 = Off, 1 = Active)

260

LBR

Loop Break (0 = Off, 1 = Active)

263

A.TUNE

Auto-tune Enable (0 = Off, 1 = Enabled)

270

A-M

Mode of the Loop (0 = Auto, 1 = Manual)

273

Ac.All

Acknowledge all alarms (1 = Acknowledge

274

L-R

Local Remote (Comms) Setpoint Select

276