Super Systems 3 Series User Manual

Page 92

Advertising
background image

Operations Manual

Series 3

92

Digital input (DigIn A/B)
Contact
closure

Contact open >600Ω Contact closed <300Ω

Input current <13mA
Isolation

None from PV or system
264Vac double insulated from PSU and communications

Functions

Include alarm acknowledge, SP2 select, manual
keylock, standby select, RSP select

Logic I/O module Output
Rating

On/High 12Vdc at <44mA
Off/Low <300mV at 100µA

Isolation

None from PV or system
264Vac double insulated from PSU and communications

Functions

Control, alarms or events

Logic I/O module Digital input
Contact
closure

Contact open >500Ω Contact closed <150Ω

Isolation

None from PV or system
264Vac double insulated from PSU and communications

Functions

Include alarm acknowledge, SP2 select, manual
keylock, standby select, RSP select

Relay output channels
Type

Form A (normally open)

Rating

Min: 12V, 100mA dc Max: 2A, 264Vac resistive

Functions

Control, alarms or events

Triac output
Rating

0.75A rms 30 to 264V rms (resistive load)

Isolation

264Vac double insulated

Functions

Control, alarms or events

Analogue output

(3)

Rating

OP1, OP2 and OP3

0-20mA into <500Ω

Accuracy

+ (<1% of reading + <100μA) [<50μA for OP3]

Resolution

13.5 bits [13.6 bits for OP3]

Isolation

264Vac double insulated from PSU and
communications.
Module code C and OP3 provides full 264V double
insulated

Functions

Control, retransmission

Note (3) Voltage output can be achieved by external adaptor

Remote SP input
Calibration Accuracy

<+ 0.25% of reading + 1LSD

Sample Rate

4Hz (250mS)

Isolation

264Vac double insulated from instrument

Resolution

<0.5mV for 0-10V input, or <2μA for 4-
20mA

Resolution (effective bits) >14 bits
Drift with temperature

<50ppm typical, <150ppm worst case

Common mode rejection

48 - 62 Hz, >-120db

Series mode rejection

48 - 62 Hz, >-90db

Input Impedance

>222Kohm (Volts) 2.49R (Current)

Normal input range

0 – 10V and 4 – 20mA

Max input range

-1V to 11V and 3.36mA to 20.96mA

Software features
Control

Number of loops

1

Loop update

250mS

Control types

PID, ON/OFF, VP

Cooling types

Linear, fan, oil, water

Modes

Auto, manual, standby, forced manual

Overshoot inhibition

High, low

Alarms

Number

3

Type

Absolute high and low, deviation high, low or
band, rate of change

Latching

Auto or manual latching, non-latching, event
only

Output assignment

Up to four conditions can be assigned to one
output

Custom messages

Number

15 scrolling text messages

No. of characters

127 characters per message max

Languages

English

Selection

Active on any parameter status using
conditional command