Series 3

Operations Manual

39

9.1.7

Output List 2 (OP-2)

This is an optional normally open relay and is available on terminals 2A and 2B. The way in which this output operates is
determined by parameters in the OP- 2 List. OP2 beacon is operated from this output channel.

OUTPUT LIST 2 ‘op-2’

Name

Scrolling

Display

Parameter Description

Value

Default

Access Level

2 . i d

OUTPUT 2
TYPE

Output channel 2 hardware
type

reLy

Relay output

As
ordered

Read only

2.FUNC

FUNCTION

Output channel 2 function
If the instrument is ordered as
valve positioner (codes VC or
VP), only options available are ,
none, d.out, UP

, or dwn

Note: If output 2 is set to Up
ensure the other valve
position output is set to dwn
and vice versa

none

Disabled. If disabled no further parameters are
shown

As
ordered

Conf

d.out

Digital output

Heat

Heat output

CooL

Cool output

2.SRC.A

I/O 2 SOURCE A

These parameters only appear
when the channel function is a
Digital OP,
i.e. 2.FUNC = d.Out

Selects an event status to be
connected to the output
channel.

The output status is the result
of an OR of Src A, Src B, Src C,
and Src D

Up to four events can,
therefore, operate the output

none

No event connected to the output

none

Conf

AL1

Alarm 1 *

2.SRC.B

I/O 2 SOURCE B

AL2

Alarm 2 *

AL3

Alarm 3 *

2.SRC.C

I/O 2 SOURCE C

AL4

Alarm4 *

ALL.A

All alarms

2.SRC.D

I/O 2 SOURCE D

nw.AL

Any new alarm

Ct.AL

CT alarm, load, leak & overcurrent

Lbr

Loop break alarm

Sbr

Sensor break alarm

mAn

Manual status

rmt.F

Remote fail

Pwr.f

Power fail

prg.e

FEATURE UNAVAILABLE

2.SENS

SENSE

To configure the polarity of
output channel 2

nor

Normal

nor

Conf

* The mnemonic for the alarm will change depending upon the alarm configuration.

9.1.8

Output List 3 (OP-3)

This is a normally 4-20 or 0-20mA isolated dc output. The way in which this output operates is determined by parameters in the
OP- 3 List. OP3 beacon is operated from this output channel.


OUTPUT LIST 3 ‘op-3’

Name

Scrolling

Display

Parameter Description

Value

Default

Access Level

3 . i d

OUTPUT 3
TYPE

Output channel 3 hardware
type

nonE

Output not fitted

As ordered

Read only

dC.Op

0-20mA output See note 1

3.FUNC

FUNCTION

Output channel 3 function
If the instrument is ordered as
valve positioner (codes VC or
VP), only options available are ,
none, d.out, UP

, or dwn

Note: If output 3 is set to Up
ensure the other valve
position output is set to dwn
and vice versa

none

Disabled. If disabled no further
parameters are shown

d.out

Conf

Heat

Heat output

CooL

Cool output

w.sp

Working setpoint re-transmission

Shown if I/O 3 TYPE = dc.OP
Retransmission

pV

Process variable re-transmission

Op

Output re-transmission

Inv

Inverted

3.rng

DC OUTPUT
RANGE

DC output calibration.
Only shown if
3 . i d = dC.Op

4.20

4-20mA

4.20

Conf

0.20

0-20mA


Note 1: A DC output may require calibration.