Operations Manual

Series 3

66

12.3

Alarm Parameters

Four alarms are available. Parameters do not appear if the Alarm Type = None. The following table shows the parameters to set
up and configure alarms.

ALARM LIST

‘ALARM’

Name

Scrolling Display

Parameter Description

Value

Default

Access
Level

A1.TYP

ALARM 1 TYPE

Selects the type of alarm

none

Alarm not configured

Conf

Hi

Full Scale High

Lo

Full Scale Low

d.Hi

Deviation High

d.Lo

Deviation Low

bnd

Deviation band

rrc

Rising rate of change,
set in 1-9999 eng
units/min

Frc

Falling rate of change
set in 1-9999 eng
units/min

A 1 . - - -

ALARM 1 SETPOINT

Alarm 1 threshold value.
The last three characters show the
type of alarm configured from the
above list

Instrument range

0

L3

A 1 . s t s

ALARM 1 OUTPUT

Indicates the status of the alarm

OFF

Alarm off

Read only

On

Alarm on

A1.HYS

ALARM 1
HYSTERESIS

See description at the beginning of
this section

0 to 9999

Conf

A1.LAT

ALARM 1
LATCHING TYPE

See description at the beginning of
this section

none

Non-latching

Conf

Auto

Latching with
automatic resetting

Man

Latching with manual
resetting

Evt

Event (no alarm
flashing beacon but
messages can be
displayed)

A1.BLK

ALARM 1
BLOCKING

See description at the beginning of
this section

No

No blocking

No

Conf

yes

Blocking

The above parameters are repeated for Alarm 2, A2; Alarm 3, A3; Alarm 4, A4