Appendix a technical specification – Super Systems 3 Series User Manual

Page 91

Advertising
background image

Series 3

Operations Manual

91


15. Appendix A TECHNICAL SPECIFICATION

General

Temperature limits

Operation: 0 to 55°C (32 to 131°F),

Storage: -10 to 70°C (14 to 158°F)

Humidity limits

Operation: RH: 5 to 90% non-condensing

Storage: RH: 5 to 90% non-condensing

Panel sealing

IP 65, Nema 4X

Shock

BS EN61010

Vibration

2g peak, 10 to 150Hz

Altitude

<2000 metres

Atmospheres

Not suitable for use above 2000m or in explosive
or corrosive atmospheres.

Electromagnetic
compatibility (EMC)

EN61326-1 Suitable for domestic, commercial
and light industrial as well as heavy industrial
environments. (Class B emissions, Industrial
Environment immunity).
Low supply voltage versions are suitable for
industrial environments only.

Installation category
II

The rated impulse voltage for equipment on
nominal 230V supply is 2500V

Pollution degree 2

Normally only non conductive pollution occurs.
Occasionally, however, a temporary
conductivity caused by condensation shall be
expected.

Physical

Series 3

Panel mounting

1/4 DIN

Weight grams

420

Operator interface

Type

LCD TN with backlight

Main PV display

4 digits green

Lower display

Series 3

5 character starburst green

Staus beacon

Units, outputs, alarms, active setpoint

Power requirements

Series 3

100 to 240Vac, -15%, +10%
48 to 62Hz, max 8W

Approvals

CE, cUL listed (file ES7766)
Suitable for use in Nadcap and AMS2750D
applications under Systems Accuracy Test
calibration conditions


Transmitter PSU
Isolation

264Vac double insulated

Output Voltage

24Vdc, >28mA, <33mA

Communications: serial communications option
Protocol

Modbus RTU slave

Isolation

264Vac double insulated

Transmission

EIA485 2-wire

standard

Process Variable Input
Calibration accuracy

<+0.25% of reading +1LSD

Sample rate

(1)

4Hz (250mS)

Isolation

264Vac double insulated from the PSU and
communications

Resolution (µV)

< 0.5µV when using a 1.6 second filter

Resolution (effective
bits)

>17 bits

Linearisation accuracy

<0.1% of reading

Drift with temperature

<50ppm (typical) <100ppm (worst case)

Common mode rejection 48 - 62 Hz, >-120db
Series mode rejection

48 - 62 Hz, >-93db

Input impedance

100MΩ

Cold junction
compensation

>30 to 1 rejection of ambient temperature

External cold junction

Reference of 0

O

Cold junction accuracy

C

<+1

o

C at 25

o

Process Linear

C ambient

-10 to 80mV, 0 to 10V with external potential
divider module 100KΩ/806Ω

Thermocouple Types

K, J, N, R, S, B, L, T, C

RTD/PT100 Type

3-wire, Pt100 DIN43760

Bulb current

0.2mA

Lead compensation

No error for 22 ohms in all 3 leads

Input filter

Off to 59.9 seconds

Zero offset

User adjustable over the full display range

User calibration

2-point gain & offset

Notes
(1) Calibration accuracy quoted over full ambient operating range
and for all input linearisation types.

AA relay
Type

Form C changeover

Rating

Min: 12V, 100mA dc Max: 2A, 264Vac resistive

Functions

Control, alarms or events