Operations Manual

Series 3

46

11.2

Control Parameters

The control loop is configured by the parameters listed in the following table:

CONTROL LIST

‘CTRL’

Parameter
Name

Parameter Description
(Scrolling Display)

Value

Default

Access
Level

C T R L . H

HEATING TYPE
Selects the channel 1 control algorithm.
Different algorithms may be selected
for channels 1 and 2. In temperature
control applications, Ch1 is usually the
heating channel, Ch2 is the cooling
channel.

Pid

PID

Conf

off

Heating off

on.of

On/Off

MTr

Valve position control (n/a)

C T R L . C

COOLING TYPE
Selects the channel 2 Control
algorithm. Different algorithms may be
selected for channels 1 and 2.
This is not available if the instrument is
a valve position controller

oFF

Cooling disable

Conf

pid

PID

on.of

On/Off

C T R L . A

CONTROL ACTION
Selects the direction of the control. i.e
reverse or direct acting.

rev

Reverse acting. Output decreases as
PV increases

rev

Conf

dir

Direct acting. Output increases as PV
decreases

P B . U N T

PROPORTIONAL BAND UNITS

enG

In engineering units

Perc

In percent

A T U N E

AUTO-TUNE ENABLE

OFF

Auto-tune off

OFF

L3

On

Set to ‘on’ to start auto-tuning

FaiL

Displayed if Autotune cannot be
completed

A T . R 2 G

AUTOTUNE CONFIGURES R2G

YES

R2G will be set by Auto-tune

yes

Conf

No

Allows a value for R2G to be entered
manually

P B

PROPORTIONAL BAND

0.1 to 9999 display units or
1 to 999.9% if proportional band expressed as %

20

L3

T I

INTEGRAL TIME

Off

to 9999 seconds

360

sec

L3

T D

DERIVATIVE TIME

Off

to 9999 seconds

TD

defaults to OFF for valve position control

60

sec

L3

R 2 G

RELATIVE COOL GAIN

0.1 to 10.0

1.0

L3

C B H i

CUTBACK HIGH

Auto

or 1to 3000 display units

Auto

=

3xPb

L3

C B L o

CUTBACK LOW

Auto

or 1 to 3000 display units

Auto

=

3XPb

L3

M R

MANUAL RESET

0.0 to 100.0% (heat only)
-100.0 to 100.0% (heat/cool)

0.0%

L3

L B T

LOOP BREAK TIME
The loop break alarm attempts to
detect loss of restoring action in the
control loop by checking the control
output, the process value and its rate of
change.
Loop break detection works for all
control algorithms: PID, VP and ON-
OFF.
Note: This is not to be confused with
load failure and partial load failure.

Off

Setting loop Break Time to OFF
disables the Loop Break Alarm

OFF

L3

1 to 9999 minutes

O P . H I

OUTPUT HIGH
Adjust to limit the maximum heating
power applied to the process

+100.0%

100.0%

L3