Series 3

Operations Manual

79

Parameter
Mnemonic

Parameter Name

Modbus Address

Decimal

12 – Auto/Manual
13 – Remote fail
14 – Power fail
15 – FEATURE UNAVAILABLE

1.SRC.B

IO Channel 1 Source B
As IO Channel 1 Source A (Modbus address 12678)

12679

1.SRC.C

IO Channel 1 Source C
As IO Channel 1 Source A (Modbus address 12678)

12680

1.SRC.D

IO Channel 1 Source D
As IO Channel 1 Source A (Modbus address 12678)

12681

1.SENS

Configures the polarity of the input or output channel (0 = Normal, 1 = Inverted)

12682

1.PLS

IO1 Time proportioning Output minimum pulse time

12706

2.ID

Output 2 Type
0 – None
1 – Relay
2 – Logic Output
3 – DC OP
4 – Triac (SSR)

12736

2.FUNC

Output 2 Channel function
0 – None (or Telemetry Output)
1 – Digital Output
2 – Heat or UP if valve position
3 – Cool or DOWN if valve position
10 – DC Output no function
11 – DC Output Heat
12 – DC Output Cool
13 – DC Output WSP retransmission
14 – DC Output PV retransmission
15 – DC Output OP retransmission

12739

2.RNG

IO Channel 2 DC Output Range
0 – 0-20mA
1 – 4-20mA

12740

2.SRC.A

Output 2 source A
As IO Channel 1 Source A (Modbus address 12678)

12742

2.SRC.B

Output 2 source B
As IO Channel 1 Source A (Modbus address 12678)

12743

2.SRC.C

Output 2 source C
As IO Channel 1 Source A (Modbus address 12678)

12744

2.SRC.D

Output 2 source D
As IO Channel 1 Source A (Modbus address 12678)

12745

2.SENS

Output 2 Polarity (0 = Normal, 1 = Inverted)

12746

2.PLS

Output 2 Time proportioning Output minimum pulse time

12770

3.ID

Output 3 Type
0 – None
1 – Relay
2 -
3 – DC OP

12800

3.FUNC

Output 3 Channel function
0 – None (or Telemetry Output)
1 – Digital Output
2 – Heat or UP if valve position
3 – Cool or DOWN if valve position
10 – DC Output no function
11 – DC Output Heat
12 – DC Output Cool
13 – DC Output WSP retransmission
14 – DC Output PV retransmission
15 – DC Output OP retransmission

12803

3.RNG

IO Channel 3 DC Output Range
0 – 0-20mA
1 – 4-20mA

12804

3.SRC.A

Output 3 source A
As IO Channel 1 Source A (Modbus address 12678)

12806

3.SRC.B

Output 3 source B
As IO Channel 1 Source A (Modbus address 12678)

12807