Series 3

Operations Manual

77

Parameter
Mnemonic

Parameter Name

Modbus Address

Decimal

4 – B Type Thermocouple
5 – N Type Thermocouple
6 – T Type Thermocouple
7 – S Type Thermocouple
8 – RTD
9 – millivolt
10 – Comms Input (see Modbus address 203)
11 – Custom Input (Downloadable)

CJ.tyP

CJC Type
0 – Auto
1 – 0 Degrees C
2- 50 Degrees C

12291

mV.HI

Linear Input High

12306

mV.LO

Linear Input Low

12307

L.TYPE

Logic Input A channel hardware type
0 – None
1 – Logic Inputs

12352

L.D.IN

Logic input A function
40 – None
41 – Acknowledge all alarms
42 – Select SP1/2
43 – Lock All Keys
44 – FEATURE UNAVAILABLE
45 – FEATURE UNAVAILABLE
46 – FEATURE UNAVAILABLE
47 – FEATURE UNAVAILABLE
48 – Auto/Manual Select
49 – Standby Select
50 – Remote setpoint
51 – Recipe select through IO1
52 – Remote key UP
53 – Remote key DOWN

12353

L.SENS

Configures the polarity of the logic input channel A (0 = Normal, 1 = Inverted)

12361

L.TYPE (LB) Logic Input B channel hardware type

0 – None
1 – Logic Inputs

12368

L.D.IN (LB)

Logic input B function
40 – None
41 – Acknowledge all alarms
42 – Select SP1/2
43 – Lock All Keys
44 – FEATURE UNAVAILABLE
45 – FEATURE UNAVAILABLE
46 – FEATURE UNAVAILABLE
47 – FEATURE UNAVAILABLE
48 – Auto/Manual Select
49 – Standby Select
50 – Remote setpoint
51 – Recipe select through IO1
52 – Remote key UP
53 – Remote key DOWN

12369

L.SENS (LB) Configures the polarity of the logic input channel B (0 = Normal, 1 = Inverted)

12377

BAUD

Baud Rate
0 – 9600
1 – 19200
2 – 4800
3 – 2400
4 – 1200

12548

PRTY

Parity setting
0 – None
1 – Even
2 – Odd

12549

DELAY

RX/TX Delay – (0 = no delay, 1 = delay) Select if a delay is required between received and transmitted comms messages.
Sometimes required when intelligent EIA232 adaptors are used.

12550

RETRN

Comms Retransmission Variable selection:
0 – Off

12551