Operations Manual

Series 3

88

14.3.5

To Calibrate Remote Setpoint Input


Connect a milli amp source to terminals HD and HE as shown.

Select Conf Level, then:

Operation

Do This

Display View

Additional Notes

Select the Calibration
List header

1.

From any display press

as many times as

necessary until the ‘CAL’ page header is displayed.

Scrolling display ‘

C A L I B R A T I O N L I S T

Select the Calibration
Phase

2.

Press

to select ‘P H A S E ’

n o n e

p h a s e

Scrolling display ‘

C A L I B R A T I O N p h a s e

Set mA source for 4mA

Select the low
calibration point

3.

Press

or

to choose ‘rm.CL’

r m.CL

p h a s e

Calibrate the
instrument to the low
calibration point (4mA)

4.

Press

to select ‘G O ’

5.

Press

or

to choose ‘YES’

Scrolling display ‘

C A L I B R A T I O N s t a r t

The controller automatically calibrates to the
injected input. The display will show

busy

then

pass

,

(if calibration is successful.) or ‘

FAIL

if not.

Fail may be due to incorrect input. mA

Set mV source for 20mA

Select the high
calibration point

9.

Press

to select ‘P H A S E ’

10. Press

or

to choose ‘rm.CH’

11. Repeat 4 and 5 above to calibrate the high point

r m.CH

p h a s e

The controller will again automatically calibrate to
the injected input mV.

If it is not successful then ‘

FAIL’

will be displayed


To calibrate the voltage input, connect a volts source to terminals HD (negative) and HF (positive). The procedure is the same as
described above but the calibration points are

Parameter

Calibration Voltage

rm.VL

0 Volts

rm.VH

10 Volts








Copper cable

Current

Source

-

+

Controller HD

HF

HE

-

+