6 transfer from normal to bypass mode – Powerware 9330 User Manual

Page 119

Advertising
background image

9--5

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

13.

Observe the following messages appear sequentially on the PPU status line:

WAITING FOR INPUT

DC STARTING

INVERTER STARTING

SYNCING

ONLINE

The inverter turns on. When the inverter reaches full voltage, UPS output contactor

K3 closes supplying power to the critical load in Normal mode. It takes less than 1

minute for the UPS to achieve Normal mode.

14.

The UPS is now operating in the Battery mode and the

BATTERY status

indicator is illuminated.

9.6 Transfer from Normal to Bypass Mode

To transfer the critical load to bypass mode, perform the following procedure:

WARNING:

In Bypass Mode, the critical load is not protected from commercial power

interruptions and abnormalities.

1.

Press the System Control pushbutton. The System Control screen appears.

2.

Select

BYPASS from the System Control menu.

Bypass Mode Requested appears on the screen.

The UPS switches to Bypass mode and the critical load is immediately supplied by

the bypass source. If the bypass source is not available, the power processor

remains on and an alarm sounds.

3.

The UPS is now operating in the bypass mode and the

BYPASS status

indicator is illuminated.
The PPU status indicates READY. System is now on bypass and UPS power

processor remains on.

WARNING:

Power is present inside the UPS and Options cabinets.