Installing options cabinet external power wiring – Powerware 9330 User Manual

Page 53

Advertising
background image

2--27

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

2.4.4

Installing Options Cabinet External Power Wiring

NOTE: Remove Options cabinet input and output conduit landing plate to punch

conduit holes.

1.

Route input and output cables to input/output terminal block. Refer to

Appendix A of this manual for wiring access information.

2.

If optional Power Distribution Module (PDM) is installed in the Options cabinet,

proceed to step 10; otherwise, proceed to step 3.

3.

If wiring a single feed system, proceed to step 4; if wiring a dual feed system,

proceed to step 6.

4.

Connect phase A, B, C, and Neutral mains and bypass input power wiring from

source to the bypass input terminals in the Options cabinet. Refer to Appendix

A of this manual for wiring and termination requirements and wiring access

information. Note wiring connections for single feed systems.

5.

Proceed to step 8.

6.

Connect phase A, B, and C mains input power wiring from source to the mains

input terminals in the Options cabinet. Refer to Appendix A of this manual for

wiring and termination requirements and wiring access information. Note

wiring connections for dual feed systems.

7.

Connect phase A, B, C, and Neutral bypass input power wiring from source to

the bypass input terminals in the Options cabinet. Refer to Appendix A of this

manual for wiring and termination requirements and wiring access information.

Note wiring connections for dual feed systems.

8.

Connect phase A, B, and C and Neutral output power wiring from output

terminals to critical load. Refer to Appendix A of this manual for wiring and

termination requirements and wiring access information.

9.

Proceed to step 17.

10.

If wiring a single feed system, proceed to step 11; if wiring a dual feed system,

proceed to step 13.

11.

Connect phase A, B, C, and Neutral mains and bypass input power wiring from

source to the bypass input terminals in the Options cabinet. Refer to Appendix

A of this manual for wiring and termination requirements and wiring access

information. Note wiring connections for single feed systems.

12.

Proceed to step 15.

13.

Connect phase A, B, and C mains input power wiring from source to the mains

input terminals in the Options cabinet. Refer to Appendix A of this manual for

wiring and termination requirements and wiring access information. Note

wiring connections for dual feed systems.

14.

Connect phase A, B, C, and Neutral bypass input power wiring from source to

the bypass input terminals in the Options cabinet. Refer to Appendix A of this

manual for wiring and termination requirements and wiring access information.

Note wiring connections for dual feed systems.

Advertising