POWER WIRING INSTALLATION NOTES

164201300---1

A---4

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

Table D. Ratings & External Wiring Requirements for

Powerware 9330 (10 kVA---20 kVA)

Options Cabinet INPUT and BYPASS Transformers

Ratings 50/60 Hz

Basic unit ratings at

Voltage

Input

Conductor

g

0.7 lagging PF load

Series/

Model

kVA/KW

Input

Output

Input

Current

(Amps)

Minimum

Size

20/10

10/7

208

208

27.8

8

20/10

10/7

480

208

12

14

20/10

10/7

600

208

9.6

14

AC Input to UPS Rectifier

20/15

15/10.5

208

208

41.6

6

AC

INPUT

p

Transformer

(0 95min PF)

20/15

15/10.5

480

208

18

12

INPUT (0.95min.PF)

3 , 1 gnd

20/15

15/10.5

600

208

14.4

12

3 , 1 gnd

20/20

20/14

208

208

55.5

4

20/20

20/14

480

208

24

10

20/20

20/14

600

208

19.2

12

20/10

10/7

208

208

27.8

8

20/10

10/7

480

208

12

14

20/10

10/7

600

208

9.6

14

AC Input to UPS Bypass

20/15

15/10.5

208

208

41.6

6

AC

INPUT

p

yp

Transformer

Full Load Current

20/15

15/10.5

480

208

18

12

INPUT Full Load Current

3 , 1 Neutral, 1 gnd

20/15

15/10.5

600

208

14.4

12

3 , 1 Neutral, 1 gnd

20/20

20/14

208

208

55.5

4

20/20

20/14

480

208

24

10

20/20

20/14

600

208

19.2

12