DESCRIPTION:

DATE:

DRAWING NO:

2 of 2

SHEET:

REVISION:

G

061502

PHYSICAL FEATURES AND REQUIREMENTS

164201300---3

A---25

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

6.

The basic environmental requirements for operation of the UPS system are:

Ambient Temperature Range:

0---40˚C (32---104˚F)

Recommended Operating Range: 20---25˚C (68---77˚F)

Maximum Relative Humidity:

95%, noncondensing

The UPS ventilation requirements are shown in Table AC.

Table AC. Air Conditioning or Ventilation Requirements

During Full Load Operation

Powerware 9330 (10 kVA--40 kVA)

Ratings

Input/Output Voltage

Heat Rejection*

BTU/hr ¢ 1000/hr (Kg---cal/hr)

208/208

2.4 (0.6)

10 KVA

480/208

3.1 (0.8)

480/480, 600/208

3.6 (0.9)

208/208

3.5 (0.9)

15 KVA

480/208

4.6 (1.1)

480/480, 600/208

5.3 (1.3)

208/208

4.7 (1.2)

20 KVA

480/208, 600/208

6.1 (1.5)

480/480

7.1 (1.8)

208/208

5.9 (1.5)

25 KVA

480/208, 600/208

7.7 (1.9)

480/480

8.9 (2.2)

208/208

7.1 (1.8)

30 KVA

480/208, 600/208

9.2 (2.3)

480/480

10.7 (2.7)

208/208

8.3 (2.1)

35 KVA

480/208, 600/208

10.8 (2.7)

480/480

12.5 (3.1)

208/208

9.5 (2.4)

40 KVA

480/208, 600/208

12.4 (3.1)

480/480

14.3 (3.6)