PHYSICAL FEATURES AND REQUIREMENTS

164201300---3

A---24

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

1.

The UPS equipment operating environment must meet the size and weight requirements

shown in Table AA, according to your UPS system configuration.

2.

In the UPS system, the UPS, Options, and Battery cabinets are palleted separately for

shipping.

3.

Do not tilt cabinets more than

10˚ during handling.

4.

Dimensions are in millimeters (inches).

Table AA Equipment Weight

Table AA. Equipment Weight

Component

Weight

Kg (lb)

Component

Shipping

Installed

Point Loading

UPS Cabinet with Filter and Batteries

Powerware 9330 (10 kVA---20 kVA)

461 (1017) 435 (958)

6 at 73 (160)

UPS Cabinet with Filter and Batteries

Powerware 9330 (25 kVA---40 kVA)

873 (1925) 838 (1847)

9 at 93 (205)

Options Cabinet with PDM and no transformer

Powerware 9330 (10 kVA---20 kVA)

118 (260)

90 (200)

4 at 23 (50)

Options Cabinet with PDM and 1 transformer

Powerware 9330 (10 kVA---20 kVA)

240 (530)

213 (470)

4 at 53 (118)

Options Cabinet with PDM and 2 transformers

Powerware 9330 (10 kVA---20 kVA)

358 (790)

331 (730)

4 at 83 (183)

Options Cabinet with PDM and no transformer

Powerware 9330 (25 kVA---40 kVA)

154 (340)

120 (265)

6 at 20 (44)

Options Cabinet with PDM and 1 transformer

Powerware 9330 (25 kVA---40 kVA)

471 (1040) 437 (965)

6 at 73 (161)

Options Cabinet with PDM and 2 transformers

Powerware 9330 (25 kVA---40 kVA)

782 (1725) 748 (1650)

6 at 125 (275)

Battery Cabinet

361 (795)

333 (735)

6 at 56 (123)

NOTES:

Powerware 9330 (10 kVA---20 kVA)

1. For UPS Cabinet without Filter, subtract 25 Kg (55 lb).

2. For UPS Cabinet without Batteries, subtract 227 Kg (499 lb)

3. For Options Cabinet without PDM, subtract 11 Kg (25 lb)

Powerware 9330 (25 kVA---40 kVA)

1. For UPS Cabinet without Filter, subtract 41 Kg (90 lb).

2. For UPS Cabinet without Batteries, subtract 453 Kg (998 lb)

3. For Options Cabinet without PDM, subtract 11 Kg (25 lb)

5.

The clearances required around the UPS System are shown in Table AB.

Table AB. System Clearances
From Front of Cabinet

36 inches working space

From Back of Cabinet

12 inches air circulation clearance

From Sides of Cabinet

Allow space for Options and Battery Cabinets