DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION: G

2 of 5

061502

CUSTOMER INTERFACE WIRING

INSTALLATION NOTES

CSB CUSTOMER INTERFACE

RELAY #2 NC

RELAY #2 RETURN
RELAY #2 NO

RELAY #1 NC

RELAY #1 RETURN
RELAY #1 NO

BUILDING ALARM #1 RETURN

BUILDING ALARM #1

BUILDING ALARM #2 RETURN

BUILDING ALARM #2

BUILDING ALARM #3 RETURN

BUILDING ALARM #3

BUILDING ALARM #4 RETURN

BUILDING ALARM #4

NOTE: All building alarm inputs or remote features require an isolated normally open contact or

switch (rated at 24 VDC, 20 mA minimum) connected between the alarm input and common

terminal as shown. All control wiring and relay and switch contacts are customer provided.

164201300---2

NOTE: Regardless of assignment, alarms display as Building Alarm 1, Building Alarm 2,

etc., on Monitor Panel. Use twisted pair wires for each alarm input and common.

TERMINAL TB4

CAN H

CAN L

RTN

TERMINAL TB7

TERMINAL TB6

TERMINAL TB2

c

COMMUNICATIONS SERVER BOARD (CSB)

REFER TO DRAWING 164201300---8

FOR LOCATION OF CSB

EXTERNAL CAN

TERMINATION

(JUMPER J40)

TERMINAL TB5

NOT USED

NOT USED

EXTERNAL EPO

EXTERNAL EPO RTN

NOT USED

RTN

A---20

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502