Ab c d – Powerware 9330 User Manual

Page 176

Advertising
background image

DESCRIPTION:

DATE:

DRAWING NO:

5 of 17

SHEET:

REVISION: D

NOTE:

Callout letter

and

map to drawing #164201300---6

,

, ,

053001

A

B

C

D

164201300---1

POWER WIRING INSTALLATION NOTES

A

B

C

D

A---6

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

Table G. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9330---40/25

(Without Options Cabinet)

Ratings

Units

Rating 50/60 Hz

Basic unit ratings at

0.7 lagging PF load

KVA

KW

25

17.5

gg g

INPUT/OUTPUT

VOLTAGE

208

AC Input to UPS Rectifier

(0.95min.PF)

Amps*

70

AC

AC Input to UPS Rectifier

(0.95min.PF)

3 , 1 gnd

Amps*

70

AC

INPUT

3 , 1 gnd

Minimum conductor size (number per  )

AWG or kcmil(ea)

3 (1)

*(Maximum amps includes full load current plus

battery recharge current)

AC

AC Input to Module Bypass (UPS Bypass)

Full Load Current

3 , (1) Neutral, (1) gnd

Amps

69.4

AC

INPUT

Full Load Current

3 , (1) Neutral, (1) gnd

Minimum conductor size (number per  )

AWG or kcmil(ea)

4 (1)

DC

INPUT

DC Input from External Battery Source to UPS

(1) positive, (1) negative, (1) gnd

VDC (Nominal)

Amps

288

64

INPUT

( ) pos t e, ( ) egat e, ( ) g d

Minimum conductor size (number per pole) (See note 8)

AWG or kcmil(ea)

4 (1)

AC

AC Output to Critical Load

Full Load Current 3  (1) Neutral (1) gnd

Amps

69.4

AC

OUTPUT

Full Load Current 3 , (1) Neutral, (1) gnd

Minimum conductor size (number per  )

AWG or kcmil(ea)

4 (1)

Table H. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9330---40/30

(Without Options Cabinet)

Ratings

Units

Rating 50/60 Hz

Basic unit ratings at

0.7 lagging PF load

KVA

KW

30

21

gg g

INPUT/OUTPUT

VOLTAGE

208

AC Input to UPS Rectifier

(0.95min.PF)

Amps*

80

AC

AC Input to UPS Rectifier

(0.95min.PF)

3 , 1 gnd

Amps*

80

AC

INPUT

3 , 1 gnd

Minimum conductor size (number per  )

AWG or kcmil(ea)

3 (1)

*(Maximum amps includes full load current plus

battery recharge current)

AC

AC Input to Module Bypass (UPS Bypass)

Full Load Current

3 , (1) Neutral, (1) gnd

Amps

83

AC

INPUT

Full Load Current

3 , (1) Neutral, (1) gnd

Minimum conductor size (number per  )

AWG or kcmil(ea)

2 (1)

DC

INPUT

DC Input from External Battery Source to UPS

(1) positive, (1) negative, (1) gnd

VDC (Nominal)

Amps

288

78

INPUT

( ) pos t e, ( ) egat e, ( ) g d

Minimum conductor size (number per pole) (See note 8)

AWG or kcmil(ea)

3 (1)

AC

AC Output to Critical Load

Full Load Current 3  (1) Neutral (1) gnd

Amps

83

AC

OUTPUT

Full Load Current 3 , (1) Neutral, (1) gnd

Minimum conductor size (number per  )

AWG or kcmil(ea)

2 (1)

Advertising