12--13

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

Inverter Version

0.97

Machine Control Version 0.99
Comm Server Version

0.98

Display Version

0.96

08/11/2000 14:13:03.000 STATUS: CSB Power Supply On

08/11/2000 14:13:03.043 NOTICE: Inverter Initializing

08/11/2000 14:13:05.721 STATUS: UPS Power Supply OK

08/11/2000 14:13:05.728 NOTICE: Input Under Voltage

08/11/2000 14:13:05.729 NOTICE: Output Under Voltage

08/11/2000 14:13:05.729 NOTICE: Bypass Under Voltage

08/11/2000 14:13:05.749 ALARM: Rectifier Under Voltage

08/11/2000 14:13:10.459 ALARM: Battery Under Voltage

08/11/2000 14:13:12.954 NOTICE: Battery Voltage Low

08/11/2000 14:13:13.165 NOTICE: Battery Not Present

08/11/2000 14:13:34.710 STATUS: PPU Shutdown

08/11/2000 14:13:57.773 NOTICE: Check Modem

08/11/2000 14:14:33.520 ALARM: Inverter Tripped

08/11/2000 14:14:33.520 ALARM: Check Inverter

08/11/2000 14:27:09.000 STATUS: CSB Power Supply On

08/11/2000 14:27:09.043 NOTICE: Inverter Initializing

08/11/2000 14:27:11.725 STATUS: UPS Power Supply OK

08/11/2000 14:27:11.733 NOTICE: Input Under Voltage

08/11/2000 14:27:11.733 NOTICE: Output Under Voltage

08/11/2000 14:27:11.733 NOTICE: Bypass Under Voltage

08/11/2000 14:27:11.754 ALARM: Rectifier Under Voltage

08/11/2000 14:27:16.464 ALARM: Battery Under Voltage

08/11/2000 14:27:18.954 NOTICE: Battery Voltage Low

08/11/2000 14:27:19.169 NOTICE: Battery Not Present

08/11/2000 14:27:40.714 STATUS: PPU Shutdown

08/11/2000 14:28:04.023 NOTICE: Check Modem

08/12/2000 14:15:09.000 STATUS: CSB Power Supply On

08/12/2000 14:15:09.043 NOTICE: Inverter Initializing

08/12/2000 14:15:11.725 STATUS: UPS Power Supply OK

08/12/2000 14:15:11.733 NOTICE: Input Under Voltage

08/12/2000 14:15:11.733 NOTICE: Output Under Voltage

08/12/2000 14:15:11.754 ALARM: Rectifier Under Voltage

08/12/2000 14:15:11.833 NOTICE: Maintenance Bypass On

08/12/2000 14:15:16.463 ALARM: Battery Under Voltage

08/12/2000 14:15:18.954 NOTICE: Battery Voltage Low

08/12/2000 14:15:19.169 NOTICE: Battery Not Present

08/12/2000 14:15:40.714 STATUS: PPU Shutdown

08/12/2000 14:16:04.023 NOTICE: Check Modem

08/12/2000 14:16:22.925 CMD: Bypass Mode Command

08/12/2000 14:16:23.443 STATUS: K5 (Backfeed) Closed

08/12/2000 14:16:23.586 STATUS: On Bypass

08/12/2000 14:16:24.860 NOTICE: Output Under Voltage OK

08/12/2000 14:17:20.900 NOTICE: Input Under Voltage OK

08/12/2000 14:17:23.606 ALARM: Rectifier Under Voltage OK

08/12/2000 14:17:25.557 ALARM: Battery Under Voltage OK

08/12/2000 14:19:01.899 CMD: PPU On Command

08/12/2000 14:19:04.089 STATUS: K1 (Input) Closed

Figure 12---18. Event History Log