15--3

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

15.4

Environmental Specifications

Operating Temperature

0 to 40˚C without derating. The recommended

operating temperature is 25˚C.

Operating Altitude

Maximum 1500m (5000 ft) at 40_C without

derating

Storage Temperature

---20 to +70˚C (prolonged storage above 40˚C

will cause rapid battery self-discharge)

Relative Humidity (operating and

storage)

95% maximum, noncondensing

Acoustical Noise

60 dBA at a 1m distance

EMI Suppression

Meets FCC Regulation 47, Part 15, for class A

devices

Electrostatic Discharge (ESD)

Immunity

Meets IEC 801---2 specifications. Withstands up

to 25 kV pulse without damage and with no

disturbance or adverse effect to the critical load.

System Efficiency at Full Unity

Power Factor Load and Nominal

Input Voltage

208V Models:

92% in Normal Mode

98% in High Efficiency Mode

480V Models:

90% in Normal Mode

96% in High Efficiency Mode

600

V Models:

90% in Normal Mode

96% in High Efficiency Mode