13 options cabinet maintenance bypass transfer, 14 using the power distribution module, 15 using the load off pushbutton – Powerware 9330 User Manual

Page 122: 1 to use the load off pushbutton

Advertising
background image

9--8

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

9.13 Options Cabinet Maintenance Bypass Transfer

To transfer the critical load to Maintenance Bypass, perform the following

procedure:

1.

Transfer critical load to bypass by performing procedure in paragraph 9.6.

2.

Manually set the Options Cabinet Maintenance Bypass Switch to

BYPASS, by

turning slowly through the

TEST position to BYPASS.

The input, output, battery and bypass backfeed contactors open and the PPU is

turned off. The maintenance bypass source supplies the critical load.

WARNING:

Power is present inside the UPS and Options cabinets

.

9.14

Using the Power Distribution Module

If the UPS system contains the optional Power Distribution Module, access to the

PDM circuit breakers can be gained by performing the following procedure.

1.

Slide the Options cabinet top cover latches to the rear of the cabinet.

2.

Lift and secure cover in the upright position using latching slide bar.

9.15

Using the LOAD OFF Pushbutton

An UPS Load Off is initiated by the red

LOAD OFF pushbutton on the UPS Control

Panel. This pushbutton can be pressed to control the UPS output. The UPS

LOAD OFF pushbutton de-energizes the critical load and powers down the UPS.
The UPS (including Bypass) remains off until restarted.

9.15.1 To Use the LOAD OFF Pushbutton

1.

Press the

LOAD OFF pushbutton.

The Unit Shutdown screen appears, providing a choice to proceed with the shutdown

or to abort the shutdown.

WARNING:

All power to the critical load is lost when

YES is selected in the following step. You

should use this feature only when you want to de-energize the critical load.

2.

To shut down the UPS, select

YES from the Unit Shutdown menu, and hold for

two seconds . To abort the shutdown, select

NO.

When YES is selected and held for two seconds, the input, output, battery and

bypass backfeed contactors open and the PPU is turned off.

CAUTION:

Do not attempt to restart the system after Load Off until the cause of the

shutdown has been identified and cleared.

3.

To restart the UPS after pressing the

LOAD OFF pushbutton, follow the

procedure, in paragraphs 9.2 or 9.3.