DESCRIPTION:

DATE:

DRAWING NO:

10 of 17

SHEET:

REVISION: F

111501

NOTE: Customer ground, size 1/0, can be

run in any conduit listed in Table R.

POWER WIRING INSTALLATION NOTES

164201300---1

A---11

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

Table O. UPS Cabinet Power Cable Terminations Powerware 9330 (25 kVA---40 kVA)

Terminal Function

Terminal

Function

Size of Pressure

Termination

Vendor

Tightening Torque

N-M (lb-in.)

Type

Screw

AC Input to UPS

A

Phase A 1

#14 #0

Entrelec

2.5-2.9(22-26)

Slotted

p

Rectifier and Bypass

(TB2)

A

Phase A 1 --- #14---#0

Phoenix

3.2-3.7(28-33)

Slotted

(TB2)

(Single Input)

B

Phase B 1

#14 #0

Entrelec

2.5-2.9(22-26)

Slotted

(Single Input)

B

Phase B 1 --- #14---#0

Phoenix

3.2-3.7(28-33)

Slotted

C

Phase C 1

#14 #0

Entrelec

2.5-2.9(22-26)

Slotted

C

Phase C 1 --- #14---#0

Phoenix

3.2-3.7(28-33)

Slotted

N

Neutral

1

#4 #4/0

Entrelec

4-6(35-52)

6 mm

N

Neutral

1 --- #4---#4/0

Phoenix

15-20(133-177)

6 mm

Allen

AC Input to UPS

C

A

Phase A 1 --- #2---#4/0

ABB

13.5(120)

3/16 i

p

Rectifier (CB1)

(Dual Input)

B

Phase B 1 --- #2---#4/0

ABB

13.5(120)

3/16 in.

Allen

(Dual Input)

C

Phase C 1 --- #2---#4/0

ABB

13.5(120)

Allen

AC Input To Bypass

A

Phase A 1

#14 #0

Entrelec

2.5-2.9(22-26)

Slotted

p

yp

(TB2)

(Dual Input)

A

Phase A 1 --- #14---#0

Phoenix

3.2-3.7(28-33)

Slotted

(Dual Input)

B

Phase B 1

#14 #0

Entrelec

2.5-2.9(22-26)

Slotted

B

Phase B 1 --- #14---#0

Phoenix

3.2-3.7(28-33)

Slotted

C

Phase C 1

#14 #0

Entrelec

2.5-2.9(22-26)

Slotted

C

Phase C 1 --- #14---#0

Phoenix

3.2-3.7(28-33)

Slotted

N

Neutral

1

#4 #4/0

Entrelec

4-6(35-52)

6 mm

N

Neutral

1 --- #4---#4/0

Phoenix

15-20(133-177)

6 mm

Allen

AC Output to Critical

A

Phase A 1

#14 #0

Entrelec

2.5-2.9(22-26)

Slotted

p

Load

(Part of TB3)

A

Phase A 1 --- #14---#0

Phoenix

3.2-3.7(28-33)

Slotted

(Part of TB3)

B

Phase B 1

#14 #0

Entrelec

2.5-2.9(22-26)

Slotted

B

Phase B 1 --- #14---#0

Phoenix

3.2-3.7(28-33)

Slotted

C

Phase C 1

#14 #0

Entrelec

2.5-2.9(22-26)

Slotted

C

Phase C 1 --- #14---#0

Phoenix

3.2-3.7(28-33)

Slotted

N

Neutral

1

#4 #4/0

Entrelec

4-6(35-52)

6 mm

N

Neutral

1 --- #4---#4/0

Phoenix

15-20(133-177)

6 mm

Allen

DC Input from

Battery to UPS

N/A

Battery

(+)

Red Battery

Connector

N/A

N/A

N/A

Battery to UPS

N/A

Battery

(---)

Black Battery

Connector

N/A

N/A

N/A

External Battery

S

Battery

Positive

1

#14 #0

Entrelec

2.5-2.9(22-26)

Slotted

y

Input to UPS

(Part of TB3)

Battery

+

Positive

1 --- #14---#0

Phoenix

3.2-3.7(28-33)

Slotted

(Part of TB3)

Battery

Negative 1

#14 #0

Entrelec

2.5-2.9(22-26)

Slotted

Battery

---

Negative 1 --- #14---#0

Phoenix

3.2-3.7(28-33)

Slotted

Customer Ground

Ground

Ground

2 --- #14---1/0

N/A

5.6 (50)

Slotted

Advertising