Powerware 9330 User Manual

Page 188

Advertising
background image

DESCRIPTION:

DATE:

DRAWING NO:

17 of 17

SHEET:

REVISION: D

053001

164201300---1

POWER WIRING INSTALLATION NOTES

A---18

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

16.

Output overcurrent protection and output disconnect switch are to be provided by the

user. Table W lists the maximum rating for output circuit breakers satisfying the criteria for

both.

Table W. Maximum Output Circuit Breaker Ratings

Powerware System

Output Voltage Rating

Powerware System

208V

480V

600V

9330---20/10

35

15

15

9330---20/15

60

25

20

9330---20/20

70

30

25

9330---40/25

90

40

30

9330---40/30

110

45

40

9330---40/35

125

60

45

9330---40/40

150

60

50

17.

Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC.

Rated battery current is computed at the computed voltage.

Advertising