Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

2.6.1

Installation Checklist

-

All packing materials and restraints have been removed from each cabinet.

-

Each cabinet in the UPS system is placed in its installed location.

-

A cabinet grounding/mounting kit is installed between any cabinets that are bolted

together.

-

All conduits, and cables are properly routed to the UPS and auxiliary cabinets.

-

All power cables are properly sized and terminated.

-

The bypass source of the supply is a four wire wye configuration. If using dual feed, the

rectifier source is a three wire connection from a wye configuration.

-

All telephone and network connections have been completed.

-

A ground conductor is properly installed.

-

Internal battery cabinet connections have been completed (plugs, etc.).

-

Air conditioning equipment is installed and operating correctly.

-

The area around the installed UPS system is clean and dust-free. (It is recommended

that the UPS be installed on a level floor suitable for computer or electronic

equipment.)

-

Adequate workspace exists around the UPS and other cabinets.

-

Adequate lighting is provided around all UPS equipment.

-

A 120V service outlet is located within 25 feet of the UPS equipment.

-

The Remote Emergency Power Off (EPO) device is mounted in its installed location

and its wiring terminated inside the UPS cabinet.

-

Summary alarms and/or building alarms are wired appropriately. (OPTIONAL)

-

Startup and operational checks performed by authorized service personnel.